LM-1302 Meter Adapter Recorder
A Versatile Meter Base "Plug-In"
Recorder. 
The LM-1302 is a Form 2S
residential meter adapter recorder designed to simply plug into a
meter base to simultaneously record power quality and power
consumption (1% accuracy). The unit has captive internal CT’s
making installation and current measurement easy.
Power Consumption
The unit records KW, KWH, Power Factor and all key power
parameters with 1% accuracy and time stamp (Internet synchronized by
modem). Customer high bill complaints are easily resolved. You can
even easily upgrade to Enetics’ unique SPEEDTM
technology which will record which individual appliances turned ON
and OFF with time stamp and individual power consumption. This not
only demonstrates to the customer that your revenue meter is correct
but where the high power consumption is coming from.
Power Quality
More and more residences have become vulnerable to power quality
problems because of home offices and so many appliances using
sensitive electronics. The LM-1302 records voltage, current, one
cycle swell and sag events, total harmonic distortion (THD%) and
even individual harmonics for trending. Easy to use software
generates charts and reports in Excel eliminating
software compatibility problems. At a glance, sags or loose neutrals
can be identified. And you still have the Excel data to
manipulate to do other calculations if necessary.
Software
All data is stored in a standard SQL database.
Charts and Reports are generated in Microsoft Excel with
canned macros avoiding compatibility problems. The data is always
available in Excel format for any analysis not covered by
our canned macros and inquiries for special reports are invited. In
addition, Enetics will make available the database format and the
macro code in the event you wish to generate your own information.
Setting up the recorder is a simple form fill-in procedure.
SPEED™ Technology
The LM-1302 is easily upgraded to incorporate Enetics’ unique
and proprietary SPEED technology (previously known as NIALMS). In
this mode, with only single point measurement (the meter), the
recorder records not only whole house power consumption but also
when individual appliances within the home turned on and off and how
much power each consumed.
Critical energy consumption information is
obtained with a single point measurement at significantly reduced
time and expense. This information can be used for:
-
Resolving High Bill Complaints.
-
Rate Structure Formulation.
-
DSM Program Verification.
-
Load Research.
- Offering Many Unique Customer Services.
Specifications
Form: 2S
Channels:
Voltage 2
Current 2
Range:
Voltage - 208/240
Current Form 2S (200A)
Memory
Non-volatile 2MB.
Sample Rate/Response Time:
32 samples/cycle
Accuracy:
Voltage - +/- 0.2% reading +
0.1% FS
Current - +/- 0.2% reading +
0.2% FS
Power - +/- 0.5%
reading + 0.01% FS
Response Time/Recording Interval
Response Time: 20 cycles
Recording Interval: 1 min to 8 hour (Wraparound)
Communications:
Internal Modem Data Rate: 2.4 kbps
Serial Port: 19.2 kbps
Power:
From line voltage
Environmental/Physical:
Operating Temp Range: -20 oC to +70 oC
|